KT-300 Combus Modules |
Five Combus modules can be connected to a KT-300:
• KT-PC4108 (8-zone input expansion module). This module has a tamper contact input.
• KT-PC4116 (16-zone input expansion module). This module has a tamper contact input.
• KT-PC4204 (4-relay/power supply expansion module). It has a tamper contact input and also includes a built-in 12VDC, 1A power supply for field devices.
• KT-PC4216 (16-zone output expansion module). It can be used for elevator control, although additional hardware may be required.
• KT-LCD3 (Kantech 32-character liquid crystal display). The LCD is green (normal status), red (power failure) and yellow (trouble).
1 - If a Combus module is installed to the KT-300 controller, click the Combus module configuration button. Undefined Combus terminals are identified by red flags/bullets. Once a module has been defined, it is identified by a green flag.
2 - To define a module, select one, then click the Define button (lower part of the window). The Enter Combus module serial number message box appears.
3 - Enter the module’s serial number, then click OK.
4 - Assign names to the modules in the language fields.
5 - Check the options related to the module you want to configure (if these are displayed in the window).
| Combus type | Options | Additional options |
|---|---|---|
| KT3-LCD | Combus low power, display date and time | No additional options |
| KT-PC4108 | Tamper alarm, Combus low power | 8-input module |
| KT-PC4116 | Tamper alarm, Combus low power | 16-input module |
| KT-PC4204 | Tamper alarm, Combus low power, Low battery, Power failure, lower auxiliary power | Used as relays (1-4) |
| KT-PC4216 | Tamper alarm, Combus low power | Used as outputs |
6 - Check the Combus low power option so that the KT-300 will report any Combus low power condition.
7 - Check Display date and time option so that LCD can display the date and time.
8 - When you have finished configuring the Combus module, click the OK button to go back to the Status relay tab.
9 - Associate
a Local
activation relay for
Power
failure,
Combus
failure and
Combus
low power
10 - Under
Priority
call type,
assign the call type option that best suits failure event reporting